Choosing an M18 Ultrasonic Sensor: Switching Output, 4–20 mA and Blind Zone
Choose the PLC interface and check both ends of target travel before ordering. Compare BEDOOK UM18 examples with a mounting and procurement checklist.
Need help selecting? Send photos of the model, nameplate and installation; quantity may be unknown.
An ultrasonic sensor can report target presence or changing distance, depending on its output. An M18 housing identifies mechanical size, not electrical function. Choose the PLC signal first, then check sensing range, near blind zone and actual target conditions.

Decide what information the PLC needs
A tote stop station may need a discrete present-or-absent signal. A lift measuring tote height may need continuous distance. These tasks can use similar-looking sensors but need different inputs and settings.
The listed UM18-T10P-C31S12-X is the switching candidate; UM18-T10I-C31S12-X is the 4–20 mA candidate. Confirm the exact suffix, wiring diagram and supply in the quotation. Do not transfer wiring or settings between models because the connector looks the same.
| Selection point | Switching application | 4–20 mA application |
|---|---|---|
| PLC input | Compatible discrete input and output polarity | Compatible current input and loop arrangement |
| Information | State at configured switching conditions | Distance represented by configured current scaling |
| Setup record | Switch point, hysteresis and output behaviour | Near and far scaling points and units |
| Fault interpretation | State during missing or invalid echo | Defined out-of-range or missing-echo response |
| Acceptance | Repeatable switching across target variations | Distance agreement across the working range |
A PLC scaling calculation is valid only after the sensor's configured endpoints are known. Do not assume 4 mA and 20 mA correspond to physical limits printed in a family table.
Check the nearest target before maximum range
The manufacturer's UM18 switching table lists a 70–1000 mm sensing range and a 0–70 mm blind zone. It distinguishes adjustment range from overall sensing range. A tote approaching to 55 mm is not acceptable simply because the sensor has a one-metre range.
In a mounting example, moving the sensor back 30 mm changes a 55 mm near distance to 85 mm. It also increases every far distance by 30 mm. Recheck both endpoints, including tilt, overrun and mounting tolerances. Being outside the nominal blind zone alone does not prove reliable detection.
Test target, background and timing
Use the actual tote surface and its least favourable expected orientation. Angled surfaces can reflect sound away, while an empty station can expose a different reflector behind the target. Include both conditions in commissioning.
Compare the exact model's response with process timing. The cited switching model lists a maximum switching frequency of 3 Hz; a sensing-distance rating does not establish whether a fast event will be captured. For nearby ultrasonic sensors, ask about mutual interference and available synchronisation arrangements.
Procurement checklist
| Send to the supplier | Include | Ask them to confirm |
|---|---|---|
| Target | Material, size, surface and possible tilt | Suitability under expected conditions |
| Geometry | Nearest and farthest face-to-target distances | Blind-zone margin and usable range |
| Interface | PLC input, supply and output type | Model suffix and pin assignment |
| Process | Travel speed and required update time | Whether the response is fast enough |
| Setup | Switch point or analog scaling | Teach procedure and saved settings |
| Abnormal conditions | Missing tote, tilted tote and empty station | Defined output and PLC interpretation |
Record accepted settings alongside installation measurements. A replacement then has a measurable commissioning target instead of an instruction to adjust it until the machine seems to work.
BEDOOK UM18 switching specifications
Product and technical references
- M18 Ultrasonic Distance Sensor, 4–20 mA — UM18-T10I-C31S12-X
- M18 Ultrasonic Switching Sensor, 70–1000 mm — UM18-T10P-C31S12-X
Pepperl+Fuchs ultrasonic sensing modes Catalog source for the example
Need help selecting? Send photos of the model, nameplate and installation; quantity may be unknown.