Selection Guides · 3 MIN READ

Choosing an M18 Ultrasonic Sensor: Switching Output, 4–20 mA and Blind Zone

Choose the PLC interface and check both ends of target travel before ordering. Compare BEDOOK UM18 examples with a mounting and procurement checklist.

Need help selecting? Send photos of the model, nameplate and installation; quantity may be unknown.

An ultrasonic sensor can report target presence or changing distance, depending on its output. An M18 housing identifies mechanical size, not electrical function. Choose the PLC signal first, then check sensing range, near blind zone and actual target conditions.

BEDOOK M18 ultrasonic sensor and cable connection.
Measure target distance from the acoustic face. The same housing size can carry different electrical outputs.

Decide what information the PLC needs

A tote stop station may need a discrete present-or-absent signal. A lift measuring tote height may need continuous distance. These tasks can use similar-looking sensors but need different inputs and settings.

The listed UM18-T10P-C31S12-X is the switching candidate; UM18-T10I-C31S12-X is the 4–20 mA candidate. Confirm the exact suffix, wiring diagram and supply in the quotation. Do not transfer wiring or settings between models because the connector looks the same.

Selection pointSwitching application4–20 mA application
PLC inputCompatible discrete input and output polarityCompatible current input and loop arrangement
InformationState at configured switching conditionsDistance represented by configured current scaling
Setup recordSwitch point, hysteresis and output behaviourNear and far scaling points and units
Fault interpretationState during missing or invalid echoDefined out-of-range or missing-echo response
AcceptanceRepeatable switching across target variationsDistance agreement across the working range

A PLC scaling calculation is valid only after the sensor's configured endpoints are known. Do not assume 4 mA and 20 mA correspond to physical limits printed in a family table.

Check the nearest target before maximum range

The manufacturer's UM18 switching table lists a 70–1000 mm sensing range and a 0–70 mm blind zone. It distinguishes adjustment range from overall sensing range. A tote approaching to 55 mm is not acceptable simply because the sensor has a one-metre range.

In a mounting example, moving the sensor back 30 mm changes a 55 mm near distance to 85 mm. It also increases every far distance by 30 mm. Recheck both endpoints, including tilt, overrun and mounting tolerances. Being outside the nominal blind zone alone does not prove reliable detection.

Test target, background and timing

Use the actual tote surface and its least favourable expected orientation. Angled surfaces can reflect sound away, while an empty station can expose a different reflector behind the target. Include both conditions in commissioning.

Compare the exact model's response with process timing. The cited switching model lists a maximum switching frequency of 3 Hz; a sensing-distance rating does not establish whether a fast event will be captured. For nearby ultrasonic sensors, ask about mutual interference and available synchronisation arrangements.

Procurement checklist

Send to the supplierIncludeAsk them to confirm
TargetMaterial, size, surface and possible tiltSuitability under expected conditions
GeometryNearest and farthest face-to-target distancesBlind-zone margin and usable range
InterfacePLC input, supply and output typeModel suffix and pin assignment
ProcessTravel speed and required update timeWhether the response is fast enough
SetupSwitch point or analog scalingTeach procedure and saved settings
Abnormal conditionsMissing tote, tilted tote and empty stationDefined output and PLC interpretation

Record accepted settings alongside installation measurements. A replacement then has a measurable commissioning target instead of an instruction to adjust it until the machine seems to work.

BEDOOK UM18 switching specifications

Product and technical references

Pepperl+Fuchs ultrasonic sensing modes Catalog source for the example

Read the technical analysis

Need help selecting? Send photos of the model, nameplate and installation; quantity may be unknown.